Descriere
Acest Acti9 iC60N este un intreruptor automat de joasa tensiune (MCB). Este un disjunctor 2P cu 2 poli protejati, curent nominal In de 20 A si curba de declansare C. Capacitatea nominala de rupere la scurtcircuit este de pana la 20 kA pentru tensiune de la 220 V c.a. la 240 V c.a. in conformitate cu standardul EN / IEC 60947-2 si 6000 A la 400 V c.a. in conformitate cu standardul EN / IEC 60898-1. Este compatibil atat cu standardul rezidential EN/IEC 60898-1, cat si cu standardul industrial EN/IEC 60947-2. Acest disjunctor protejeaza circuitele la scurtcircuit si suprasarcina. Indicatorul VisiTrip reduce timpul de interventie, semnalizand declansarea la defect. Banda sa verde VisiSafe garanteaza deschiderea fizica a contactelor pentru a permite interventia in aval. Mecanismul sau de inchidere rapida, independent de operarea manuala, imbunatateste durata de serviciu. Are o anduranta electrica de pana la 10000 de cicluri si o anduranta mecanica de pana la 20000 de cicluri. Tensiunea de izolare nominala Ui este de 500 V c.a. Limitarea curentului de scurcircuit de clasa 3 (in conformitate cu standardul SR EN 60898-1) permite optimizarea costului protectiilor din aval. Produsul poate fi instalat pe o sina DIN. Latimea sa este de 4 module de 9 mm. Gradul de poluare este 3. Categoria de supratensiune este IV. Culoarea produsului este alb (RAL9003). Dimensiunile sunt (L) 36mm x (I) 85mm x (a) 78.5mm. Greutatea este de 0,25 kg. In conformitate cu standardul SE EN 60529, gradul de protectie este IP20 si IP40 in cofret. Temperatura de functionare este de la -35°C la 70°C. Temperatura de depozitare este de la -40°C la 85°C.
Documente
Specificatii
Other | |
Frequency | 50 Hz |
Pollution degree | 3 |
Measurements | |
Built-in depth | 44.5 mm |
Width in number of modular spacings | 2 |
Electrical | |
Rated insulation voltage Ui | 500 V |
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V | 6 kA |
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V | 20 kA |
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V | 6 kA |
Rated impulse withstand voltage Uimp | 6 kV |
Rated current | 20 A |
Rated voltage | 400 V |
Release characteristic | C |
Voltage type | AC/DC |
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V | 10 kA |
Overvoltage category | 4 |
Current limiting class | 3 |
Model/type | |
Number of poles (total) | 2 |
Number of protected poles | 2 |
Options | |
Additional equipment possible | Yes |
Concurrently switching neutral conductor | No |
Protection | |
Degree of protection (IP) | IP20 |
Explosion-proof | No |
Mounting/installation | |
Flush-mounted installation | No |
Connection | |
Connectable conductor cross section solid-core | 1 mm² |
Connectable conductor cross section multi-wired | 1 mm² |
Operating conditions | |
Ambient temperature during operating | -35 °C |
Package 1 | |
volume | 263,625 cm3 |
weight | 225 g |
length | 9,5 cm |
width | 3,7 cm |
qmax | 1 |
qmin | 1 |
um | C62 |
gtin | 3606480079573 |
Package 2 | |
volume | 1867,5 cm3 |
weight | 1,411 kg |
length | 22,5 cm |
width | 10 cm |
qmax | 6 |
qmin | 6 |
um | BX |
gtin | 13606480079570 |
Package 3 | |
volume | 36000 cm3 |
weight | 16,011 kg |
length | 40 cm |
width | 30 cm |
qmax | 66 |
qmin | 66 |
um | CT |
gtin | 43606480079571 |
Package 4 | |
weight | 145 kg |
length | 120 cm |
width | 80 cm |
qmax | 528 |
qmin | 528 |
um | PF |