Descriere
Acest produs Acti9 iCV40 este un intreruptor automat cu protectie diferentiala (RCBO). Este un disjunctor 1P+N cu 1 pol protejat, 16 A in curent nominal si curba de declansare B. Protectia diferentiala este de tip A, cu o sensibilitate de 30 mA. Temporizarea protectiei pentru scurgeri la pamant este instantanee. Capacitatea nominala de rupere la scurtcircuit Icn este de pana la 10000 A in conformitate cu standardul SR EN 61009-2-1. Acest produs protejeaza la scurtcircuit, suprasarcina, impotriva electrocutarii si impotriva incendiilor. Cei 2 indicatori unici Visitrip reduc timpul de interventie prin indicarea circuitului defect si identificarea rapida a tipului de defect. Banda sa verde VisiSafe garanteaza deschiderea fizica a contactelor pentru a permite interventia in aval. Acest produs este in conformitate cu standardul SR EN 61009-2-1. Are o anduranta electrica de pana la 20000 de cicluri si o anduranta mecanica de pana la 20000 de cicluri. Tensiunea operationala nominala Ue este de pana la 230 V c.a. Tensiunea de izolare nominala Ui este de 400 V c.a.. Tensiunea nominala de rezistenta la impuls Uimp este de 4 kV. Frecventa este de 50/60 Hz. Se monteaza pe sina DIN. Latimea in module de 9 mm este de 4. Culoarea produsului este alb (RAL9003). Dimensiunile sunt (L) 36mm x (I) 85mm x (a) 73mm. Greutatea este de 210g. In conformitate cu standardul SE EN 60529, gradul de protectie este IP20 si IP40 in cofret. Temperatura de functionare este de la -25°C la 60°C. Temperatura de depozitare este de la -40°C la 85°C.
Documente
Specificatii
Measurements | |
Built-in depth | 44 mm |
Width in number of modular spacings | 2 |
Model/type | |
Number of poles (total) | 2 |
Number of protected poles | 1 |
With interlocking device | Yes |
Electrical | |
Rated insulation voltage Ui | 400 V |
Rated fault current | 0.03 A |
Rated short-circuit breaking capacity according to IEC 60947-2 | - |
Rated short-circuit breaking capacity Icn according to EN 61009-1 | 10 kA |
Rated impulse withstand voltage Uimp | 4 kV |
Leakage current type | A |
Rated current | 16 A |
Rated voltage | 230 V |
Release characteristic | B |
Voltage type | AC |
Surge current capacity | 0.25 kA |
Overvoltage category | 3 |
Current limiting class | 3 |
Rated short-circuit breaking capacity according to EN 61009 | 10 kA |
Protection | |
Degree of protection (IP) | IP20 |
Options | |
Anti-nuisance tripping version | No |
Concurrently switching neutral conductor | Yes |
Mounting/installation | |
Flush-mounted installation | No |
Other | |
Frequency | 50/60 Hz |
Pollution degree | 3 |
Connection | |
Connectable conductor cross section solid-core | 1 mm² |
Connectable conductor cross section multi-wired | 1 mm² |
Disconnection characteristic | Undelayed |
Operating conditions | |
Ambient temperature during operating | -25 °C |
Package 1 | |
volume | 328 cm3 |
weight | 218 g |
length | 10 cm |
width | 8,2 cm |
qmax | 1 |
qmin | 1 |
um | C62 |
gtin | 3606489444532 |
Package 2 | |
volume | 36000 cm3 |
weight | 12,355 kg |
length | 40 cm |
width | 30 cm |
qmax | 54 |
qmin | 54 |
um | CT |
gtin | 43606489444530 |