CIRCUIT BREAKER SIZE S00 FOR MOTOR PROTECTION, CLASS 10 A-RELEASE 0.7...1 A N-RELEASE 13 A SCREW TER
Cod produs: 3RV2011-0JA10
Descriere
Circuit breaker size S00
Circuit breaker size S00 for motor protection provides reliable shutdown in the event of a short-circuit and protects against overload.
Technical details:
- CLASS 10 A-release 0.7...1 A
- N-release 13 A
- Screw terminal
- Standard switching capacity
- Circuit breaker SIRIUS 3RV2
- Optimized for use in load feeders and IE3/IE4 motors
- Worldwide approvals (e.g. IEC and UL/CSA)
- Applications in hazardous areas (ATEX or IEC Ex)
- Device versions for motor protection, plant protection, and short-circuit protection
- Available with screw or spring-type terminals
- Optional integral auxiliary switch
- Comprehensive range of standardized accessories
- Different energy infeed options available, such as SIRIUS 3RV29 infeed system
- Replaces the well-proven 3RV1 series
- SIRIUS modular system
Customer benefits:
- Reliable shutdown in the event of a short-circuit
- Protection against overload
- Low heat loss
- Compact and climate-proof design
- Fast, maintenance-free and vibration-proof connection
- Simple and efficient modular system
- Always up to date with comprehensive accessories
- Considerable reduction in main circuit wiring
Disclaimer: Generated by AI.
Documente
Specificatii
| Electrical | |
| With integrated under voltage release | No |
| Number of poles | 3 |
| Rated operation power at AC-3, 230 V | 0.2 |
| Rated short-circuit breaking capacity Icu at 400 V, AC | 100 |
| Rated operation power at AC-3, 400 V | 0.25 |
| Rated operating voltage | 690 |
| Overload release current setting | 0.7 |
| Power loss | 7.25 |
| Rated permanent current Iu | 1 |
| Adjustment range undelayed short-circuit release | 13 |
| Other | |
| Switch off technique | Magnetic |
| Device construction | Built-in device fixed built-in technique |
| Measurements | |
| Width | 45 |
| Depth | 97 |
| Height | 97 |
| Protection | |
| Degree of protection (IP) | IP20 |
| Connection | |
| Type of electrical connection of main circuit | Screw connection |
| Options | |
| Phase failure sensitive | Yes |
| Model/type | |
| Type of control element | Other |
| With thermal overload protection | Yes |
| With integrated auxiliary switch | No |
| Package 1 | |
| weight | 0,341 |
| length | 0,102 |
| width | 0,049 |
| qmax | 1 |
| qmin | 1 |
| um | PA |
| gtin | 4011209712393 |
| Package 2 | |
| volume | 0,026 |
| weight | 9,98 |
| length | 0,44 |
| width | 0,325 |
| qmax | 28 |
| qmin | 28 |
| um | CT |
| gtin | 4011209712393 |
| Dimensions of product | |
| Weight | 0,341 |